BS5467
Armoured Power and Control Cable
Cable Construction
Cable Construction →Technical Library
Comparing an aluminium alternative, specifying low-smoke wiring or dealing with interference on instrument signals? Explore the Prysm Cable cable constructions for each problem, how their materials and layers help, and the technical evidence behind the choice.
Technical Library
Copper is often the practical choice when cable space and equipment connections are tight. Aluminium is worth considering for larger fixed feeders when conductor cost and weight matter. A useful price comparison starts with cables sized for the same electrical duty, including the connections needed at each end.
Read MoreA building specification can require XLPE insulation and LSZH bedding and sheath in the same cable. XLPE describes the insulation around the conductor; LSZH describes smoke and halogen-related characteristics. An XLPE/PVC cable therefore meets a different material requirement from an XLPE/LSZH cable.
Read MoreFor an individual AC phase, aluminium wire armour avoids the magnetic losses associated with steel armour around a single core. That is why our single-core 11 kV cable uses AWA, while the three-core 11 kV range uses SWA. The aluminium is in the armour; both of these ranges have copper power conductors.
Read MoreAn overall screen surrounds the complete group of pairs. Individual screens surround each pair, helping reduce coupling between circuits inside the cable. For several low-level analogue loops sharing one cable, the pair-by-pair separation can be the important difference. A screen around the outside cannot provide the same internal boundaries.
Read MoreAn emergency circuit may need to keep working during a fire. An LSZH cable addresses smoke and halogen-related characteristics; a flame-retardant cable addresses flame spread. Neither label alone establishes circuit survival. Choosing the cable starts with the required function of the circuit during the fire.
Read MoreThe two figures describe different electrical stresses: 6.35 kV from conductor to earth and 11 kV between phases. They are the U₀/U rating. A higher voltage used during a cable test is a separate test condition, not permission to operate that cable continuously on a higher-voltage network.
Read MoreA cable that can be bent into position is not automatically suitable for repeated machine movement. For a tight route, the useful numbers are the finished cable diameter, the minimum bending radius for that use, and the handling-temperature limit. Conductor class alone cannot answer all three questions.
Read More“4 × 25 mm²” describes four conductors, each with a nominal area of 25 mm². It does not describe the cable’s outside diameter. Pair counts, conductor area and finished diameter each answer a different ordering question; mixing them up can produce the wrong cable or the wrong gland.
Read MoreStandards and Testing
Find products under the standard in your specification, then read the linked guide to understand its scope.
Catalogue references link to related cable products. Certification is documented separately for the applicable product and scope.
BS5467
Cable Construction
Cable Construction →BS6622
Voltage Designations
Voltage Designations →BS6724
Insulation and Outer Materials
Insulation and Outer Materials →BS6708
Conductor and Protective Layers
Conductor and Protective Layers →PAS5308 / BS5308
Screen Positions
Screen Positions →IEC60332 / BSENIEC60332
Flame Propagation
Flame Propagation →IEC61034 / BSEN50268
Smoke Characteristics
Smoke Characteristics →IEC60754 / BSEN50267 / BSENIEC60754
Gas Characteristics
Gas Characteristics →Cable Construction
Already know the required layers? Filter by conductor, insulation, screen, armour and outer sheath.
Product Data
Print a product summary or download its listed construction and technical data as CSV.
Technical Library
LSZH concerns smoke and halogen-related properties. For LSZH fixed wiring, explore 6491B/H07Z-R; for fire-alarm circuits, explore the enhanced alarm range; for fire-resistant mains, explore F2. The required fire-test classification needs evidence for the offered cable.
An individual screen surrounds each pair; an overall screen surrounds the grouped pairs. Choose the arrangement required by the instrument schedule. Our armoured Type 2 LSZH option includes both individual and collective screens.
Our single-core copper 11 kV feeder uses aluminium wire armour; our three-core copper 11 kV feeder uses steel wire armour. Choose the armour and core arrangement required by the AC circuit design.