Cable Selection Guide

Why Single-Core AC Cables Use Aluminium Wire Armour

For an individual AC phase, aluminium wire armour avoids the magnetic losses associated with steel armour around a single core. That is why our single-core 11 kV cable uses AWA, while the three-core 11 kV range uses SWA. The aluminium is in the armour; both of these ranges have copper power conductors.

Updated 7 November 2026

The Problem with Steel Around One AC Phase

Alternating current produces a changing magnetic field around the conductor. Ferromagnetic steel around an individual phase can add magnetic losses and heating. Selecting a non-magnetic armour material addresses that problem while retaining wire armour around the cable.

In a three-core cable, the phases are grouped within the same armour. Their magnetic fields largely cancel under balanced operation, allowing the familiar steel-wire-armoured construction. Three separate single-core cables do not become one multicore cable simply because they run beside each other.

AWA Does Not Mean an Aluminium Power Conductor

AWA means aluminium wire armour. It says nothing by itself about the metal carrying the load current. Our BS6622 single-core 11 kV range has compacted copper conductors, XLPE insulation, copper-tape screening, AWA and a PVC sheath.

Confusing the armour metal with the conductor metal changes the electrical design unnecessarily. In an enquiry or comparison, “copper conductor, AWA” is a useful description: it identifies the load-carrying material and the mechanical armour separately.

The Armour Choice Does Not Finish the Circuit Design

Non-magnetic metal can still have voltage induced in it. With single-core cables, screen and armour bonding therefore need attention even when the armour is aluminium. Cable spacing, circuit length, load and bonding arrangement affect the result.

A bonded metallic loop can carry circulating current; a different bonding arrangement changes the induced-voltage and protection considerations. The correct arrangement belongs to the complete circuit design. “AWA” is not a reason to ignore bonding or to treat single-point and both-end bonding as interchangeable.

Single-Core and Three-Core 11 kV Options

Our BS6622 single-core AWA and three-core SWA ranges both have a stated rating of 6350/11000 V. The difference is how the phases and protective layers are arranged, rather than one option having an aluminium conductor.

A project specifying single-core circuits needs the appropriate cable formation, supports, accessories and bonding design. A project specifying a three-core assembly needs the corresponding three-core termination and handling arrangement. The two product ranges allow those designs to be priced as different cable systems.

Our Two BS6622 11 kV Constructions

Swipe or scroll to compare the columns.

Our Two BS6622 11 kV Constructions
FeatureSingle-Core AWAThree-Core SWA
Power conductorCopperCopper
Voltage rating6350/11000 V6350/11000 V
InsulationXLPEXLPE
Metallic screenCopper tapeCopper tape
ArmourAluminium wireGalvanised steel wire
Outer sheathPVCPVC