Cable Selection Guide

Individual or Overall Screens for Instrument Cables?

An overall screen surrounds the complete group of pairs. Individual screens surround each pair, helping reduce coupling between circuits inside the cable. For several low-level analogue loops sharing one cable, the pair-by-pair separation can be the important difference. A screen around the outside cannot provide the same internal boundaries.

Updated 7 November 2026

Start with Where the Interference Comes From

A cable carrying several instrument loops can face two different problems: electrical noise arriving from nearby equipment and coupling between the circuits within its own jacket. The screen position changes which boundary is protected.

An overall foil surrounds the assembled bundle. Individual foils put another boundary around each pair. A construction with both individual and overall screens combines those positions; adding steel-wire armour addresses mechanical protection, not the same signal-screening job.

When Individual Screens Earn Their Place

Consider a multipair run between field junction boxes and a control panel. Several low-level analogue signals may share the route, with different loop references and sensitivities. Individual pair screens help limit coupling between those neighbouring circuits.

Where the instrument design requires only collective screening, an overall-screened cable may be the appropriate and simpler construction. The choice follows the signals and the interference path. A higher screen count is not a substitute for choosing the correct pair arrangement and electrical characteristics.

A Good Screen Still Needs a Good Installation

The screen has to remain part of the intended grounding and termination system. A drain wire provides a practical connection to a foil screen; it is separate from the signal conductors and should not be counted as an extra instrument core.

Ground-potential differences can also introduce noise. This is why a universal instruction to bond every instrument screen at one end, or at both ends, is too broad. The instrument manufacturer’s requirements and the plant grounding design determine the connection. Route separation from power cables and sound terminations remain important even with individually screened pairs.

Three Prysm Cable Screen Arrangements

Our PAS5308 ranges provide the screen choices below. The two Type 1 options differ in screen position and sheath material. The Type 2 option combines individual and collective screens with steel-wire armour and LSZH outer materials.

Match the Screen and the Route

Swipe or scroll to compare the columns.

Match the Screen and the Route
CableScreen PositionCoverings and Mechanical Layer
Part 1 Type 1 overall screenedCollective aluminium/Mylar foilPE insulation; PVC sheath
Part 1 Type 1 individually screened LSZHIndividual pair screensPE insulation; LSZH sheath
Part 1 Type 2 individually screened LSZHIndividual and collective foil screensPE insulation; galvanised SWA; LSZH bedding and sheath

[1] [2] [3]

Keep Signal Requirements Alongside the Screen Choice

Two screened cables can still differ in conductor size, pair count, capacitance and suitability for the connected instrument or protocol. For a replacement, retaining the required pair arrangement and electrical characteristics matters as much as retaining the word “screened”.

Cable Options in This Article