SPWC-CABLE-008
BS5467 3 Core Mains Cable 3.3kV - XLPE, SWA, PVC
BS5467 3 Core Mains Cable 3.3kV - XLPE, SWA, PVC - 16mm to 400mm
Three-core BS 5467 cable for fixed 3.3 kV power feeders. It combines Class 2 copper conductors and XLPE insulation in one steel-wire-armoured, PVC-sheathed cable, with a 1900/3300 V rating.
| Core Arrangement | 3 Core |
|---|---|
| Rated Voltage | 1900/3300 Volts |
| Temperature Range | Fixed -20°C to +90°C |
Product Details
One Cable Entry for Three Power Cores
The three-core assembly brings the phase conductors into the equipment through one cable entry. A feeder designed around separate power cables needs a different cable arrangement. For the three-core format with LSZH bedding and sheath, compare our BS 6724 3.3 kV mains cable.
Product Details
Cable Construction
01Conductor
Class 2 stranded copper conductor acc BS EN 60228 (previously BS 6360)
02Insulation
Cross-Linked Polyethylene (XLPE)
03Bedding / Inner Sheath
Polyvinyl Chloride (PVC)
04Armour
Steel Wire Armour (SWA)
05Outer Sheath
Polyvinyl Chloride PVC
Product Details
Electrical and Physical Specifications
- Rated Voltage
- 1900/3300 Volts
- Temperature Range
- Fixed -20°C to +90°C
- Core Arrangement
- 3 Core
Product Details
Standards and Technical Topics
Copper or Aluminium Cable? Cost, Space and Installation
Copper is often the practical choice when cable space and equipment connections are tight. Aluminium is worth considering for larger fixed feeders when conductor cost and weight matter. A useful price comparison starts with cables sized for the same electrical duty, including the connections needed at each end.
Read MoreXLPE or LSZH? You May Need Both
A building specification can require XLPE insulation and LSZH bedding and sheath in the same cable. XLPE describes the insulation around the conductor; LSZH describes smoke and halogen-related characteristics. An XLPE/PVC cable therefore meets a different material requirement from an XLPE/LSZH cable.
Read MoreWhy Single-Core AC Cables Use Aluminium Wire Armour
For an individual AC phase, aluminium wire armour avoids the magnetic losses associated with steel armour around a single core. That is why our single-core 11 kV cable uses AWA, while the three-core 11 kV range uses SWA. The aluminium is in the armour; both of these ranges have copper power conductors.
Read MoreProduct Details
Product Technical Data
BS5467 3 Core Mains Cable 3.3kV - XLPE, SWA, PVC
Compare with Another Cable
Product Comparison
Cable Constructions Side by Side
Choose two cable products to compare their construction, ratings and stated service conditions.
| Construction Field | BS5467 3 Core Mains Cable 3.3kV - XLPE, SWA, PVC | BS6622 3 Core Mains Cable 11kV - XLPE, SWA, PVC |
|---|---|---|
| Conductor | Class 2 stranded copper conductor acc BS EN 60228 (previously BS 6360) | Stranded Plain Annealed Circular Compacted Copper Conductors |
| Insulation | Cross-Linked Polyethylene (XLPE) | Cross-Linked Polyethylene (XLPE) |
| Bedding / Inner Sheath | Polyvinyl Chloride (PVC) | Polyvinyl Chloride (PVC) |
| Armour | Steel Wire Armour (SWA) | Galvanised Steel Wire Armour |
| Outer Sheath | Polyvinyl Chloride PVC | PVC outer sheath |
| Screen | Not Listed | Individual or overall copper tape screen |
| Rated Voltage | 1900/3300 Volts | 6350/11000 Volts - Tested to Voltage and Duration of BS 6622 |
| Temperature Range | Fixed -20°C to +90°C | -15°C to +90°C |
| Core Arrangement | 3 Core | 3 Core |
| Standard Reference | BS5467 · BS EN/IEC 60332 | BS6622 · BS EN60332 · IEC 60502 |
Product Details
Cable Manufacturing and Packing
Cable Manufacturing


Reel Packing and Restraints