SPWC-CABLE-122
N2XS(F)2Y 11kV Medium Voltage Power Cable - XLPE, PE
N2XS(F)2Y 11kV Medium Voltage Power Cable - XLPE, PE - 35mm to 630mm
Copper medium-voltage power cable rated 6/10 (12) kV, with XLPE insulation and a PE sheath. The N2XS(F)2Y construction includes a copper-wire screen and counter-helix copper tape.
| Rated Voltage | 6/10 (12)kV |
|---|---|
| Temperature Range | 0°C to +70°C |
Product Details
Use the Complete Voltage Designation
The full 6/10 (12) kV rating is the value to match to the network specification. The range title’s 11 kV shorthand is not a substitute for that designation. Network earthing and equipment requirements determine whether the selected cable voltage class fits.
Product Details
Cable Construction
01Conductor
Stranded Copper Conductor to BS EN 60228
02Insulation
Cross-Linked Polyethylene (XLPE)
03Screen
Copper Wire Screen & Counter Helix Copper Tape
04Outer Sheath
Polyethylene (PE)
Product Details
Electrical and Physical Specifications
- Rated Voltage
- 6/10 (12)kV
- Temperature Range
- 0°C to +70°C
Product Details
Standards and Technical Topics
What 6.35/11 kV Means on an MV Cable
The two figures describe different electrical stresses: 6.35 kV from conductor to earth and 11 kV between phases. They are the U₀/U rating. A higher voltage used during a cable test is a separate test condition, not permission to operate that cable continuously on a higher-voltage network.
Read MoreXLPE or LSZH? You May Need Both
A building specification can require XLPE insulation and LSZH bedding and sheath in the same cable. XLPE describes the insulation around the conductor; LSZH describes smoke and halogen-related characteristics. An XLPE/PVC cable therefore meets a different material requirement from an XLPE/LSZH cable.
Read MoreCable Size: Cores, Pairs, mm² and Outside Diameter
“4 × 25 mm²” describes four conductors, each with a nominal area of 25 mm². It does not describe the cable’s outside diameter. Pair counts, conductor area and finished diameter each answer a different ordering question; mixing them up can produce the wrong cable or the wrong gland.
Read MoreProduct Details
Product Technical Data
N2XS(F)2Y 11kV Medium Voltage Power Cable - XLPE, PE
Compare with Another Cable
Product Comparison
Cable Constructions Side by Side
Choose two cable products to compare their construction, ratings and stated service conditions.
| Construction Field | N2XS(F)2Y 11kV Medium Voltage Power Cable - XLPE, PE | N2XS(F)2Y 22kV Medium Voltage Power Cable - XLPE, PE |
|---|---|---|
| Conductor | Stranded Copper Conductor to BS EN 60228 | Not Listed |
| Insulation | Cross-Linked Polyethylene (XLPE) | XLPE |
| Screen | Copper Wire Screen & Counter Helix Copper Tape | Not Listed |
| Outer Sheath | Polyethylene (PE) | PE |
| Rated Voltage | 6/10 (12)kV | Not Listed |
| Temperature Range | 0°C to +70°C | Not Listed |
| Voltage Designation | Not Listed | 22kV |
| Standard Reference | BS EN / IEC 60332-1-2 · VDE 0276-620 · BS EN 60228 | BS EN / IEC 60332-1-2 · VDE 0276-620 · BS EN 60228 |
Product Details
Cable Manufacturing and Packing
Cable Manufacturing


Reel Packing and Restraints