F120 Enhanced Fire Resistant Mains Cable 1kV - BS7846, BS8491, MGT, XLPE, SWA, LSZH
F120 Enhanced Fire Resistant Mains Cable 1kV - BS7846, BS8491, MGT, XLPE, SWA, LSZH - 4mm to 16mm
F120 enhanced fire-resistant mains cable for 600/1000 V circuits, with BS 7846 and BS 8491 references. The 4–16 mm² construction combines copper, XLPE insulation, steel-wire armour and LSZH outer materials.
| Rated Voltage | 600/1000 volts |
|---|---|
| Temperature Range | -10°C to +90°C |
Product Details
Specify the Fire-Test Classification
The project’s required BS 8491 classification needs to match the test evidence for the ordered cable. The F120 product name alone is not a 120-minute performance report. Our larger F120 range covers 25–400 mm² feeder sizes.
Product Details
Cable Construction
01Conductor
Plain Annealed Stranded Copper Conductor
02Insulation
Cross-Linked Polyethylene (XLPE)
03Bedding / Inner Sheath
LSZH
04Armour
Galvanised Steel Wire Armour
05Outer Sheath
Low Smoke Zero Halogen (LSZH)
Product Details
Electrical and Physical Specifications
- Rated Voltage
- 600/1000 volts
- Temperature Range
- -10°C to +90°C
Product Details
Standards and Technical Topics
XLPE or LSZH? You May Need Both
A building specification can require XLPE insulation and LSZH bedding and sheath in the same cable. XLPE describes the insulation around the conductor; LSZH describes smoke and halogen-related characteristics. An XLPE/PVC cable therefore meets a different material requirement from an XLPE/LSZH cable.
Read MoreLSZH, Flame Retardant or Fire Resistant: Which Cable Does the Circuit Need?
An emergency circuit may need to keep working during a fire. An LSZH cable addresses smoke and halogen-related characteristics; a flame-retardant cable addresses flame spread. Neither label alone establishes circuit survival. Choosing the cable starts with the required function of the circuit during the fire.
Read MoreWill the Cable Fit the Bend and Survive the Movement?
A cable that can be bent into position is not automatically suitable for repeated machine movement. For a tight route, the useful numbers are the finished cable diameter, the minimum bending radius for that use, and the handling-temperature limit. Conductor class alone cannot answer all three questions.
Read MoreProduct Details
Product Technical Data
F120 Enhanced Fire Resistant Mains Cable 1kV - BS7846, BS8491, MGT, XLPE, SWA, LSZH
Compare with Another Cable
Product Comparison
Cable Constructions Side by Side
Choose two cable products to compare their construction, ratings and stated service conditions.
| Construction Field | F120 Enhanced Fire Resistant Mains Cable 1kV - BS7846, BS8491, MGT, XLPE, SWA, LSZH | F120 Enhanced Fire Resistant Mains Cable 1kV - BS7846, BS8491, MGT, XLPE, SWA, LSZH |
|---|---|---|
| Conductor | Plain Annealed Stranded Copper Conductor | Plain Annealed Stranded Copper Conductor |
| Insulation | Cross-Linked Polyethylene (XLPE) | Cross-Linked Polyethylene (XLPE) |
| Bedding / Inner Sheath | LSZH | Low Smoke Zero Halogen (LSZH) |
| Armour | Galvanised Steel Wire Armour | Galvanised Steel Wire Armour |
| Outer Sheath | Low Smoke Zero Halogen (LSZH) | Low Smoke Zero Halogen (LSZH) |
| Rated Voltage | 600/1000 volts | 600/1000 volts |
| Temperature Range | -10°C to +90°C | -10°C to +90°C |
| Standard Reference | BS7846 · BS8491 · BS EN 50267 · BS EN 50268 · BS 6387 · BS8519-2020 · IEC 60754 · BS EN 50265 · BS EN 50266 · IEC 60332-3 · IEC 61034 | BS7846 · BS8491 · BS EN 50267 · BS EN 50268 · BS 6387 · BS8519-2020 · IEC 60754 · BS EN 50265 · BS EN 50266 · IEC 60332-3 · IEC 61034 |