SPWC-CABLE-043
BS6708 Type 7M Mining Cable - EPR, CP
BS6708 Type 7M Mining Cable - EPR, CP - 16mm to 150mm
Type 7M mining cable for power connections requiring screens over both phase and pilot cores. It uses flexible tinned copper, EPR insulation and a heavy-duty chloroprene sheath, with an uninsulated ground core.
| Rated Voltage | 640V to 1100V |
|---|---|
| Temperature Range | Fixed: -20°C to +85°C |
Product Details
Screening the Pilot as Well as the Phases
Choose Type 7M where the machine specification calls for a screened pilot. The neighbouring Type 7 range screens the phases but leaves the pilot unscreened. The pilot requirement is the useful distinction between these two arrangements, rather than conductor size alone.
Product Details
Cable Construction
01Conductor
Electrolytic, stranded, tinned copper wire IEC 60228 Class 5
02Insulation
Ethylene propylene rubber (EPR) Ground core is not insulated
03Screen
Tinned copper / Nylon braided screen over phase and pilot cores
04Bedding / Inner Sheath
Rubber based bedding compound
05Outer Sheath
Heavy duty chloroprene outer sheath
Product Details
Electrical and Physical Specifications
- Rated Voltage
- 640V to 1100V
- Temperature Range
- Fixed: -20°C to +85°C
Product Details
Standards and Technical Topics
XLPE or LSZH? You May Need Both
A building specification can require XLPE insulation and LSZH bedding and sheath in the same cable. XLPE describes the insulation around the conductor; LSZH describes smoke and halogen-related characteristics. An XLPE/PVC cable therefore meets a different material requirement from an XLPE/LSZH cable.
Read MoreWhy Single-Core AC Cables Use Aluminium Wire Armour
For an individual AC phase, aluminium wire armour avoids the magnetic losses associated with steel armour around a single core. That is why our single-core 11 kV cable uses AWA, while the three-core 11 kV range uses SWA. The aluminium is in the armour; both of these ranges have copper power conductors.
Read MoreIndividual or Overall Screens for Instrument Cables?
An overall screen surrounds the complete group of pairs. Individual screens surround each pair, helping reduce coupling between circuits inside the cable. For several low-level analogue loops sharing one cable, the pair-by-pair separation can be the important difference. A screen around the outside cannot provide the same internal boundaries.
Read MoreProduct Details
Product Technical Data
BS6708 Type 7M Mining Cable - EPR, CP
Compare with Another Cable
Product Comparison
Cable Constructions Side by Side
Choose two cable products to compare their construction, ratings and stated service conditions.
| Construction Field | BS6708 Type 7M Mining Cable - EPR, CP | BS6708 Type 7 Mining Cable - EPR, CP |
|---|---|---|
| Conductor | Electrolytic, stranded, tinned copper wire IEC 60228 Class 5 | Electrolytic, stranded, tinned copper wire IEC 60228 Class 5 |
| Insulation | Ethylene propylene rubber (EPR) Ground core is not insulated | Ethylene propylene rubber (EPR) Ground core is not insulated |
| Screen | Tinned copper / Nylon braided screen over phase and pilot cores | Tinned copper / Nylon braided screen over phase cores. Pilot core is not screened. |
| Bedding / Inner Sheath | Rubber based bedding compound | Rubber based bedding compound |
| Outer Sheath | Heavy duty chloroprene outer sheath | Heavy duty chloroprene outer sheath |
| Rated Voltage | 640V to 1100V | 640V to 1100V |
| Temperature Range | Fixed: -20°C to +85°C | Fixed: -20°C to +85°C |
| Standard Reference | BS6708 | BS6708 |
Product Details
Cable Manufacturing and Packing
Cable Manufacturing


Reel Packing and Restraints